GreenLight Request a quote
Drag to rotate the model

GL-A1 Industrial Heat Pump, 45–350 kW

For industrial sites, hotels, schools, greenhouses and pools: heating, cooling and DHW, capacity from 45 to 350 kW.

Model

Heating capacity (water 30/35 °C)
45 kW
Power input / COP (30/35 °C)
10.3 / 4.36 kW / —
Cooling capacity / EER
30 / 2.53 kW / —
Noise level
≤62 dB(A)
Dimensions (L×W×H)
1252×1076×1870 mm
Net weight
450 kg

What is the GL-A1 heat pump

Industrial heat pumps for large sites: factories, hotels, schools, greenhouses and pools. Heating, cooling and hot water, capacity from 45 to 350 kW.

How the GL-A1 heat pump works

The heat pump takes heat from outdoor air and heats water for the building's heating system, and switches to cooling in summer. Even at −12 °C outside it supplies 55 °C water.

GL-A1 heat pump: advantages

  • Operates at outdoor temperatures from −25 to +48 °C
  • Heats water to 55 °C even at −12 °C outside
  • Electronic expansion valve for precise operation
  • After-sales service: first year free

GL-A1 heat pump: specifications

ParameterGL-050A1GL-100A1GL-200A1GL-400A1
Power supply, V/Ph/Hz 380–415 / 3 / 50380–415 / 3 / 50380–415 / 3 / 50380–415 / 3 / 50
Heating capacity (water 30/35 °C), kW 4590180350
Power input / COP (30/35 °C), kW / — 10.3 / 4.3620.8 / 4.3242.0 / 4.2581.4 / 4.30
Heating capacity (water 50/55 °C), kW 3667167328
COP (50/55 °C), — 2.322.632.952.88
Heating capacity at −12 °C (water 55 °C), kW 2440107205
COP at −12 °C, — 1.551.601.981.96
Cooling capacity / EER, kW / — 30 / 2.5360 / 2.62140 / 3.19268 / 3.05
Max. power input, kW 16.836.570.1145.0
Max. current, A 31.563.3132.5260.0
Expansion valve Saginomiya / EEVSaginomiya / EEVDanfoss / EEVDanfoss / EEV
Water flow, m³/h 8163260
Water pressure drop, kPa 50504850
Operating temperature, °C −25…+48−25…+48−25…+48−25…+48
Noise level, dB(A) ≤62≤67≤70≤76
Protection rating IPX4IPX4IPX4IPX4
Net weight, kg 45080013302186
Dimensions (L×W×H), mm 1252×1076×18702198×1096×21762300×1150×24502800×2200×2450
Water connection DN40DN50Фланец DN80Фланец DN100

Specifications are based on manufacturer data under standard test conditions and are subject to change.