Drag to rotate the model The 3D model is not available in this browser.
FP Wall-mounted Water Fan Coil
Ultra-slim wall-mounted fan coil for cooling and heating. Built-in drain pump lifts condensate up to 290 mm.
Model
- Heating capacity (60 °C)
- 5.4 kW
- Cooling capacity (7 °C)
- 3.5 kW
- Airflow
- 750 m³/h
- Noise level
- 33–45 dB
- Net dimensions (L×W×H)
- 860×195×280 mm
- Net / gross weight
- 8.9 / 9.3 kg
- Heating capacity (60 °C)
- 5.4 kW
- Cooling capacity (7 °C)
- 3.5 kW
- Airflow
- 750 m³/h
- Noise level
- 18–33 dB
- Net dimensions (L×W×H)
- 850×210×265 mm
- Net / gross weight
- 10 / 11 kg
- Heating capacity (60 °C)
- 5.4 kW
- Cooling capacity (7 °C)
- 5.6 kW
- Airflow
- 750 m³/h
- Noise level
- 31–46 dB
- Net dimensions (L×W×H)
- 890×188×315 mm
- Net / gross weight
- 9.2 / 9.3 kg
- Heating capacity (60 °C)
- 9.22 kW
- Cooling capacity (7 °C)
- 5.42 kW
- Airflow
- 1020 m³/h
- Noise level
- 33–47 dB
- Net dimensions (L×W×H)
- 970×233×315 mm
- Net / gross weight
- 11.48 / 13.5 kg
- Heating capacity (60 °C)
- 11.25 kW
- Cooling capacity (7 °C)
- 7.5 kW
- Airflow
- 1700 m³/h
- Noise level
- 39 dB
- Net dimensions (L×W×H)
- 1750×510×360 mm
- Net / gross weight
- 35 / 40 kg
What is the FP wall fan coil
A wall-mounted indoor unit for a heat pump system: heats the room in winter and cools it in summer. It looks like an air conditioner but runs on water from the heat pump.
How the FP wall fan coil works
Water from the heat pump flows through the fan coil — warm in winter and cold in summer — while a fan blows room air through its heat exchanger. Condensate is removed by the built-in drain pump.
FP wall fan coil: advantages
- Heating up to 11.25 kW and cooling up to 7.5 kW
- Power input of only 33–60 W
- Built-in drain pump, condensate lift up to 290 mm
- Ultra-slim casing
FP wall fan coil: specifications
| Parameter | FP-2PSY | FP-2PGD | FP-2PLY | FP-3PJY | FP-4PFL |
|---|---|---|---|---|---|
| Airflow, m³/h | 750 | 750 | 750 | 1020 | 1700 |
| Cooling capacity (7 °C), kW | 3.5 | 3.5 | 5.6 | 5.42 | 7.5 |
| Heating capacity (60 °C), kW | 5.4 | 5.4 | 5.4 | 9.22 | 11.25 |
| Power input, W | 33 | 18 | 33 | 35 | 60 |
| Noise level, dB | 33–45 | 18–33 | 31–46 | 33–47 | 39 |
| Net dimensions (L×W×H), mm | 860×195×280 | 850×210×265 | 890×188×315 | 970×233×315 | 1750×510×360 |
| Packed dimensions, mm | 920×340×280 | 910×335×280 | 955×390×245 | 1050×390×315 | 1820×435×585 |
| Net / gross weight, kg | 8.9 / 9.3 | 10 / 11 | 9.2 / 9.3 | 11.48 / 13.5 | 35 / 40 |
Specifications are based on manufacturer data under standard test conditions and are subject to change.